Mass. penalizes Aquarion Water Company for drinking water violation

Aug. 3, 2022
Valve and probe malfunctions caused about eight gallons of undiluted potassium hydroxide to flow into a pipe at Aquarion’s water treatment plant, raising pH values to as high as 11 at one location.

The Massachusetts Department of Environmental Protection (MassDEP) has assessed a $13,500 penalty to the Aquarion Water Company of Massachusetts for violating drinking water regulations during the operation of its community public water system in the Town of Oxford.

Aquarion owns the Oxford public water system and operates and maintains four wells and three water treatment plants in town and distributes drinking water to 6,130 customers. The violation came as a result of multiple mechanical failures in the water treatment plant’s potassium hydroxide feed system.

Potassium hydroxide is added to the drinking water at the Oxford water treatment plants to increase the water's pH for corrosion control purposes. The pH of undiluted potassium hydroxide ranges from 10 to 13; solutions with pH values at or above 11 can cause skin and eye irritations and possible exacerbation of skin disorders.

On June 21, 2021, the company notified MassDEP that a customer on Depot Road reported "slippery" water while showering, resulting in a skin rash. The company immediately investigated and found the pH at the customer's home and in other parts of the system to be 10, but as high as 11 at one location in the distribution system. The company immediately took corrective measures by issuing a reverse-911 call to affected customers and flushing the distribution lines to reduce the elevated pH in the drinking water. Normal pH levels of the drinking water in the Oxford system range from 7 to 7.5.

The elevated pH in the distribution system was determined to be caused by an overfeed of potassium hydroxide at the North Main Street water treatment plant. The overfeed was due to a malfunction of a valve that allowed approximately eight gallons of undiluted potassium hydroxide to flow into a pipe at the water treatment plant. The pH probe at the water treatment plant failed to detect the elevated pH from the chemical slug in the pipe, activate the alarm system and shut down pumps to prevent unsafe drinking water from being delivered to the customers. The valve and pH probe at the North Main Street treatment plant were subsequently replaced.

Under a consent order signed with MassDEP, the company must pay the penalty and hire a third-party company to conduct a comprehensive evaluation of all existing critical chemical feed systems at Aquarion's water treatment plants in Oxford and the Town of Millbury and provide a report identifying any corrective measures needed with a schedule for completion subject to MassDEP's review and approval.

In addition, they must hire a third-party company to review and update Aquarion's Standard Operating Procedures (SOP) for its existing critical chemical feed systems to ensure its pH analyzers are properly managed and calibrated to measure a minimum pH of 10, and maintain a log documenting all testing of alarms and equipment maintenance. The revisions to the SOP and schedule for implementation are subject to MassDEP's review and approval.

"Proper operations and maintenance of components to critical chemical feed systems such as a pH analyzer at water treatment facilities are essential to ensure the delivery of safe drinking water to its users," said Mary Jude Pigsley, director of MassDEP's Central Regional Office in Worcester. "It is important to test the components routinely and document those test results to ensure the safety system works as intended."

Sponsored Recommendations

ArmorBlock 5000: Boost Automation Efficiency

April 25, 2024
Discover the transformative benefits of leveraging a scalable On-Machine I/O to improve flexibility, enhance reliability and streamline operations.

Rising Cyber Threats and the Impact on Risk and Resiliency Operations

April 25, 2024
The world of manufacturing is changing, and Generative AI is one of the many change agents. The 2024 State of Smart Manufacturing Report takes a deep dive into how Generative ...

State of Smart Manufacturing Report Series

April 25, 2024
The world of manufacturing is changing, and Generative AI is one of the many change agents. The 2024 State of Smart Manufacturing Report takes a deep dive into how Generative ...

SmartSights WIN-911 Alarm Notification Software Enables Faster Response

March 15, 2024
Alarm notification software enables faster response for customers, keeping production on track